SBWR-2280/240d temperature transmitter with thermocouple or thermal resistor is a temperature transmission unit of DDZ-S series instrument. It combines thermocouple or thermal resistor with transmitter to measure temperature of liquid, vapor and gas media within -200~1600℃. It will convert thermocouple or thermal resistor signal into 4~20mA output signal and send to display, recording instrument or computer. As a new type of temperature transmitter, it is widely used in metallurgy, petroleum, chemical, electric power, light industry, textile, food, defense and scientific research departments.
	 
	Platinum RTD
	Accuracy grade:A or B grade
	Indexing number:Pt100      resistance at 0℃:R0=100±0.06Ω(A grade)
	R0=100±0.12Ω(B grade)
	Allowable bias Δt(℃):
	Pt100±(0.15+0.002∣t∣)(A grade)
	Pt100±(0.30+0.005∣t∣)(B grade)
	Cu50±0.1%R0
	Cu100±0.1%R0
	Thermal response time:Т0.5<90S
	Transmitter Parts
	input:thermal resistance:Pt100、Cu50、Cu100
	thermocouple:K.E.S.B.T.N.
	output: 4~20mA DC signal
	basic error: Δ=Δ1+Δ2
	Δ1 allowable output error of thermocouple or thermal resistor.
	Δ2 basic output error of transmitter Δ2=±0.5%FS
	Transmission type:Two-wire
	Power voltage: Min. 12V,Max. 35V,rated voltage 24V。
	Load resistance: RL(max)=50×(Vmin-12)( 24V, load resistance 0~600Ω,rated resistance 250Ω)
	Working condition:
	a. ambient temperature:-25℃~80℃(<70℃ in dangerous place)。
	b. RH:5%~95%。
	c. mechanical frequency :f≤55Hz,amplitude <0.15mm
	d. without corrosive gas in ambient
	e. affect of ambient temperature:≤0.05%/1℃
	□ Model
	
		
			
				| 
					 
						S  
				 | 
				
					 
						B  
				 | 
				
					 
						W  
				 | 
				
					 
						□  
				 | 
				
					 
						Output  properties  
				 | 
				
					 
						sensor  
				 | 
				
					 
						Circuit  Type 
				 | 
				
					 
						Device Type 
				 | 
				
					 
						installation 
				 | 
			
			
				| 
					 
						DDZ-S series instrument 
				 | 
				
					 
						Transmission 
					
						unit  
				 | 
				
					 
						temperature  
				 | 
				
					 
						R thermocouple 
					
						  
					
						Z Thermal resistor 
					
						  
				 | 
				
					 
						2) output and hydraulic temperature is linear 
					
						  
					
						4) output and input signal for hydraulic linear 
					
						  
				 | 
				
					 
						0) Universal Thermocouple  
						1) E Nickel-chromium - copper-nickel 
						2) K Ni-Cr - Ni-Si 
						3) 
					
						 S Platinum Rhodium 10 - Platinum 
						4) 
					
						B Platinum Rhodium 30 - Platinum-rhodium 6 
						5) TCopper - Copper Nickel 
						8)NNi-Cr-Si - Ni-Si thermal resistor  
					
						1) Cu50 Copper resistance  
						2) Cu100 Copper resistance 
						4)Pt100  RTD  
				 | 
				
					 
						5)isolated 
					
						6)not isolated 
					
						  
					
						  
				 | 
				
					 
						0) normal type 
					
						 1) 
					
						 intelligent type  
				 | 
				
					 
						No) conventional type 
					
						T) special use 
					
						G) hanging wall type 
					
						D) rail type 
				 |