What are the installation technical requirements of Plug-in vortex flowmeter
Release time:2017-01-04   Clicks:75

Plug-in vortex flowmeter installation technical requirements: the former straight pipe length is not less than 40D; straight pipe length after not less than 5D; on the pipeline with gas welding open a hole slightly smaller than ф100mm and burrs around the hole cleaned to ensure smooth rotation of the probe; flange welded on the pipe hole at the manufacturer's request to the pipe axis perpendicular to the axis of the flange; ball valve and sensor mounted on welded flange; adjusting screw, the insertion depth to meet the requirements fluid flow must be maintained and indication arrow icon on the consistent uniform tighten the gland cap screws; electrical interface cable should be bent into a U-shaped, avoid water along the cable into the amplifier shell; meter installation point should stay around there is some room to install wiring and regular maintenance.
 