{_ComName}

Contact us

Shanghai Automation Instrumentation Co., Ltd.
Address:No.191 Guangzhong Road (West) Shanghai
Tel:86-21-59189606
Fax:86-21-60917975
Website:www.sc-saic.com/english
E-mail: tom.saic@gmail.com

What are the installation technical requirements of Plug-in vortex flowmeter
Release time:2017-01-04   Clicks:982

Plug-in vortex flowmeter installation technical requirements: the former straight pipe length is not less than 40D; straight pipe length after not less than 5D; on the pipeline with gas welding open a hole slightly smaller than ф100mm and burrs around the hole cleaned to ensure smooth rotation of the probe; flange welded on the pipe hole at the manufacturer's request to the pipe axis perpendicular to the axis of the flange; ball valve and sensor mounted on welded flange; adjusting screw, the insertion depth to meet the requirements fluid flow must be maintained and indication arrow icon on the consistent uniform tighten the gland cap screws; electrical interface cable should be bent into a U-shaped, avoid water along the cable into the amplifier shell; meter installation point should stay around there is some room to install wiring and regular maintenance.
 

Shanghai Automation Instrumentation Co., Ltd. Copyright Address:No.191 Guangzhong Road (West) Shanghai
Website:www.sc-saic.com/english Code: GoogleSitemap
 Companyname:Tom Tel:86-21-59189606 Mobile:15021127601
ICP:

Tel
0086-21-59189606
Fax
0086-21-60917975
My status
My status